Oil Immersed Transformer Buchholz Relay: Working Principle & Troubleshooting Guide

What is a Buchholz Relay?

The Buchholz relay, also known as a gas relay, is a core mechanical protection device exclusively fitted on conservator-type oil immersed transformers. It is mounted horizontally inside the pipeline connecting the transformer main tank and conservator tank, designed to detect internal incipient faults and severe arcing faults by capturing gas accumulation and oil surge flow.

As a standard safety component for oil immersed transformers above 500kVA, Buchholz relay can capture early hidden faults before overcurrent protection responds, greatly reducing risks of transformer burning and explosion.

At Xinhong Electrical, all our oil immersed transformers are equipped with reliable Buchholz relays complying with IEC and GB standards, fully tested before factory delivery for power distribution, industrial plant, mining and grid projects worldwide.

Working Principle of Buchholz Relay

The Buchholz relay operates in two independent protection stages: gas accumulation alarm and oil surge trip. It works purely mechanically without external auxiliary power supply.

Stage 1: Gas Accumulation – Minor Fault Alarm

When minor internal faults occur inside the oil immersed transformer, such as core overheating, loose connection, partial discharge or insulation aging, transformer oil and solid insulation will decompose slowly and produce non-soluble gas. The gas rises and gathers in the upper chamber of the Buchholz relay, displacing insulating oil and lowering the oil level.

As the oil level drops to the setting threshold, the upper float falls and closes the alarm contact, sending an alarm signal to the control room. The transformer can keep running temporarily, which gives maintenance engineers time to inspect and solve developing faults before deterioration.

Common sources of collected gas: slow thermal decomposition of insulation materials, air trapped after oil filling or transformer maintenance.

Stage 2: Oil Surge – Severe Fault Trip

Once serious internal faults take place, such as inter-turn short circuit, phase-to-ground fault or heavy electric arc, massive energy release sharply increases internal pressure. This creates high-speed oil surge rushing from main tank towards conservator.

The fast oil flow hits the baffle plate inside the Buchholz relay. When oil velocity exceeds the preset operating value, the baffle triggers the trip contact, sending a trip command to open the circuit breaker and isolate the transformer from the grid immediately to prevent catastrophic damage.

 Additional Protection: Low Oil Level Protection

When oil leakage happens, continuous oil loss will first trigger gas alarm, and if oil level keeps dropping, it will also activate trip protection to protect the transformer.

Common Alarm & Trip Faults and Troubleshooting Guide

Important reminder: After Buchholz relay alarm or trip, do NOT put transformer back into service without full inspection.

Case 1: Buchholz Relay Gas Alarm (No Trip)

Possible Causes

  1. Air trapped inside transformer after oil filtration, refilling or on-site installation (most frequent false alarm)
  2. Minor insulation aging, local overheating or loose internal connections
  3. Small oil leakage leading to slow oil level reduction

Troubleshooting Steps

  1. Record alarm time and gas volume, collect gas sample via the sampling valve of Buchholz relay
  2. Observe gas color and smell; send gas for DGA (Dissolved Gas Analysis) lab test to judge fault nature
  3. Check transformer external oil leakage, conservator oil level and breather condition
  4. If confirmed as trapped air: bleed gas from relay chamber, reset alarm and monitor continuously
  5. If DGA shows fault gas: stop load and carry out internal inspection

Case 2: Buchholz Relay Trip Action

Possible Causes

  1. Severe internal short circuit, winding arc fault or tap-changer failure
  2. Massive oil decomposition with rapid gas expansion
  3. Extreme mechanical impact or pipeline deformation causing false oil surge

Troubleshooting Steps

  1. Immediately isolate transformer and lock out power supply
  2. Collect gas sample, inspect relay window and check oil condition
  3. Carry out insulation resistance test, winding resistance test and transformer oil test
  4. Check relay installation slope, pipeline blockage and relay mechanical integrity
  5. Only after full fault elimination and qualified tests can the transformer be recommissioned

Common False Alarm & False Trip Causes

  • Wrong installation inclination angle (the pipeline must keep required upward slope towards conservator)
  • Strong mechanical vibration from surrounding equipment
  • Relay float stuck or reed contact aging
  • Improper oil pumping speed during oil filling

Installation & Maintenance Tips for Buchholz Relay

  1. Mounting requirement: The connecting pipe shall maintain a 2% ~ 4% upward slope from transformer tank to conservator to ensure gas flows into Buchholz relay smoothly.
  2. Regular inspection: Check relay observation window, oil level and sampling valve every maintenance cycle.
  3. Periodic function test: Simulate alarm and trip function during transformer overhaul.
  4. Wiring inspection: Prevent secondary circuit short or loose wiring that causes wrong signal output.

Limitations of Buchholz Relay

It is necessary to understand its application boundary for transformer protection design:

  • Only applicable to conservator-type oil immersed transformers
  • It can only detect faults under the oil level
  • Cannot detect faults on transformer bushings and outgoing cables; separate protection is required
  • Not fitted for sealed transformers without conservator

Why Choose Oil Immersed Transformers from Xinhong Electrical?

Xinhong Electrical is a professional transformer manufacturer based in China. We produce oil immersed transformers and dry type transformers ranging from 100kVA to 25MVA up to 35kV, fully equipped with high-performance Buchholz relay, pressure relief valve, temperature indicator and other protection devices.

All our transformers pass ISO, CE and CB certification. We provide custom design, factory test reports, on-site technical consultation and after-sales support for global EPC contractors, power utilities and industrial buyers. If you need technical support about Buchholz relay setting or transformer protection scheme, contact our engineering team anytime.

FAQ

Q1: Does every oil immersed transformer need a Buchholz relay?

A: Buchholz relay is standard for conservator-type oil immersed transformers generally above 500kVA. Sealed oil transformers without conservator do not adopt Buchholz relay.

Q2: What is the difference between gas alarm and oil surge trip?

A: Gas alarm is for slow gas accumulation and early warning, transformer can keep operating temporarily. Oil surge trip is triggered by fast oil flow under severe fault, which cuts off power supply immediately.

Q3: Can we reset Buchholz relay directly after gas alarm?

A: Not recommended. You need to collect gas and analyze the root cause first. If it is real internal fault, direct reset may lead to serious transformer failure.