The Buchholz relay, also known as a gas relay, is a core mechanical protection device exclusively fitted on conservator-type oil immersed transformers. It is mounted horizontally inside the pipeline connecting the transformer main tank and conservator tank, designed to detect internal incipient faults and severe arcing faults by capturing gas accumulation and oil surge flow.
As a standard safety component for oil immersed transformers above 500kVA, Buchholz relay can capture early hidden faults before overcurrent protection responds, greatly reducing risks of transformer burning and explosion.
At Xinhong Electrical, all our oil immersed transformers are equipped with reliable Buchholz relays complying with IEC and GB standards, fully tested before factory delivery for power distribution, industrial plant, mining and grid projects worldwide.
The Buchholz relay operates in two independent protection stages: gas accumulation alarm and oil surge trip. It works purely mechanically without external auxiliary power supply.
When minor internal faults occur inside the oil immersed transformer, such as core overheating, loose connection, partial discharge or insulation aging, transformer oil and solid insulation will decompose slowly and produce non-soluble gas. The gas rises and gathers in the upper chamber of the Buchholz relay, displacing insulating oil and lowering the oil level.
As the oil level drops to the setting threshold, the upper float falls and closes the alarm contact, sending an alarm signal to the control room. The transformer can keep running temporarily, which gives maintenance engineers time to inspect and solve developing faults before deterioration.
Common sources of collected gas: slow thermal decomposition of insulation materials, air trapped after oil filling or transformer maintenance.
Once serious internal faults take place, such as inter-turn short circuit, phase-to-ground fault or heavy electric arc, massive energy release sharply increases internal pressure. This creates high-speed oil surge rushing from main tank towards conservator.
The fast oil flow hits the baffle plate inside the Buchholz relay. When oil velocity exceeds the preset operating value, the baffle triggers the trip contact, sending a trip command to open the circuit breaker and isolate the transformer from the grid immediately to prevent catastrophic damage.
When oil leakage happens, continuous oil loss will first trigger gas alarm, and if oil level keeps dropping, it will also activate trip protection to protect the transformer.
Important reminder: After Buchholz relay alarm or trip, do NOT put transformer back into service without full inspection.
Possible Causes
Troubleshooting Steps
Possible Causes
Troubleshooting Steps
It is necessary to understand its application boundary for transformer protection design:
Xinhong Electrical is a professional transformer manufacturer based in China. We produce oil immersed transformers and dry type transformers ranging from 100kVA to 25MVA up to 35kV, fully equipped with high-performance Buchholz relay, pressure relief valve, temperature indicator and other protection devices.
All our transformers pass ISO, CE and CB certification. We provide custom design, factory test reports, on-site technical consultation and after-sales support for global EPC contractors, power utilities and industrial buyers. If you need technical support about Buchholz relay setting or transformer protection scheme, contact our engineering team anytime.
A: Buchholz relay is standard for conservator-type oil immersed transformers generally above 500kVA. Sealed oil transformers without conservator do not adopt Buchholz relay.
A: Gas alarm is for slow gas accumulation and early warning, transformer can keep operating temporarily. Oil surge trip is triggered by fast oil flow under severe fault, which cuts off power supply immediately.
A: Not recommended. You need to collect gas and analyze the root cause first. If it is real internal fault, direct reset may lead to serious transformer failure.