Oil Systems in Oil-Immersed Transformers

Jan 5th,2026 419 Views
An oil-immersed transformer consists of several independent oil systems. During the operation of the transformer, the oil in these systems is not interconnected, and their oil quality and operating conditions vary. Chromatographic analysis of gases dissolved in the oil should be performed separately for each system to identify potential issues.

I. Oil in High-Voltage Outlet Boxes or Gas Outlet Boxes

The high-voltage outlets of three-phase 500kV transformers adopt a corrugated insulated oil-separation system. The main function of this oil system is insulation. For structural simplification, the oil system can also be connected to the oil system in the main tank via connecting pipes or designed as an independent oil system.

II. Fully Sealed Oil Systems (for Voltage Levels of 60kV and Above)

This oil system primarily serves as insulation, or as oil that enhances the electrical strength of insulating paper in capacitor bushings. When filling oil into the main tank, the terminal ends of the bushings must be sealed to prevent air ingress.

III. Oil in On-Load Tap Changer (OLTC) Compartments

This part of the oil has its own maintenance system, including flow relays, oil conservators, and pressure relief valves. The oil in the OLTC compartment functions as insulation and arc quenching medium. When the switch interrupts the load current, the arc generated will be extinguished by the oil. The oil system must have excellent sealing performance, which should be maintained even under arc pressure during switching operations.
Although the oil in the OLTC compartment is isolated from the oil in the main tank, vacuum oil filling for both systems should be carried out simultaneously during the vacuum oiling process to avoid damaging the seals of the OLTC compartment. Both systems must maintain the same vacuum level during vacuum oil filling. If necessary, the oil conservator of this system should also be plugged during the vacuuming process. For structural convenience, the oil conservator of the main tank and that of the OLTC compartment are designed as an integrated unit with mutual isolation.

IV. Main Tank Oil System

The oil system connected to the oil surrounding the windings is the main system, including the oil in coolers or radiators, the oil in the main oil conservator, and the oil in oil-filled bushings for 35kV and below. During oil filling, the air trapped in the oil system must be released through vent plugs. Generally, each of the aforementioned components should be equipped with its own vent plug. The oil in the main tank primarily serves insulation and heat dissipation purposes.

Electrical Strength of Insulating Cardboard

During vacuum oil filling, if certain components cannot withstand the same vacuum intensity as the main tank, temporary valves (such as the gate valve between the oil conservator and the main tank) should be used for blocking. The head of the submersible pump on the cooler should be sufficient to prevent air inhalation due to negative pressure. The oil system must be equipped with a pressure relief device to relieve pressure in the event of equipment failure.

V. General Requirements for Oil Systems

  1. Before conducting various insulation tests on the oil-immersed transformer, the gas potentially trapped in the system must first be released through the vent plugs.
  2. Chromatographic analysis can predict potential issues by detecting the gas content in the oil of each system.
  3. Each oil system must meet operational requirements, such as accommodating oil volume changes during oil expansion and contraction, and being equipped with oil drain valves, vent plugs, isolation valves between coolers/radiators and the main tank, etc.
  4. All oil systems must have reliable sealing performance.
  5. The oil in the OLTC compartment can be replaced independently without draining the oil from the main tank.
  6. During transportation, the oil in the main tank can be drained and replaced with dry nitrogen for protection.