Categories

Preventive Measures for Winding Deformation in Dry-Type Transformers

Jan 5th,2026 289 Views

I. Analysis of Causes for Winding Deformation

Winding deformation in dry-type transformers refers to the change in the geometric shape of the winding structure during operation. This phenomenon severely affects the electrical performance and mechanical strength of the transformer, and may even lead to equipment failure. To effectively prevent winding deformation, it is first necessary to understand its underlying causes.
  1. Electromagnetic Force Action: Under the impact of short-circuit current, the windings are subjected to enormous electromagnetic forces, which can be divided into radial forces and axial forces. Radial forces cause the windings to expand outward or compress inward, while axial forces result in vertical displacement or tilting of the windings.
  2. Thermal Stress Impact: Temperature changes cause the winding materials to expand or contract. Differences in the thermal expansion coefficients of different materials generate thermal stress, which may lead to winding deformation under long-term action.
  3. Mechanical Vibration: Electromagnetic vibration during transformer operation and external mechanical vibration will gradually loosen the winding fasteners, reducing structural stability.
  4. Manufacturing Process Defects: Manufacturing issues such as loose winding, improper selection of insulation materials, and non-standard curing processes can 埋下 hidden dangers of deformation.
  5. Operating Environment Factors: Environmental conditions such as humidity, temperature fluctuations, and pollution accelerate the aging of insulation materials, reducing the mechanical strength of the windings.

II. Preventive Measures in the Design Phase

1. Reasonable Winding Structure Design

  • Adopt a multi-layer segmented winding structure to enhance mechanical stability of the windings.
  • Design appropriate supporting structures, such as adding reinforcing components like spacers and pressure plates.
  • Optimize the axial and radial dimension ratio of the windings to improve short-circuit resistance.

2. Material Selection and Matching

  • Select copper conductor materials with high mechanical strength.
  • Choose insulation materials with matched thermal expansion coefficients to reduce thermal stress.
  • Use high-strength interlayer insulation and end insulation materials.

3. Electromagnetic Force Calculation and Optimization

  • Accurately calculate the electromagnetic force distribution under short-circuit conditions.
  • Optimize the balance of electromagnetic forces by adjusting the winding arrangement.
  • Design a reasonable ampere-turn balance to reduce axial unbalanced forces.

III. Manufacturing Process Control

1. Winding Process

  • Strictly control the winding tension to ensure the windings are tight and uniform.
  • Use automatic winding equipment to ensure process consistency.
  • Strengthen interlayer insulation treatment to prevent local loosening.

2. Curing Process Control

  • Optimize the curing temperature curve to ensure full curing of insulation materials.
  • Adopt the Vacuum Pressure Impregnation (VPI) process to improve the integrity of the windings.
  • Control the temperature gradient during curing to reduce internal stress.

3. Assembly Quality Control

  • Ensure the assembly accuracy of windings and iron cores.
  • Reasonably set the compression device to maintain appropriate compression force.
  • Check that the torque values of all fasteners meet requirements.

IV. Operation and Maintenance Measures

1. Operation Monitoring

  • Regularly conduct winding resistance tests to monitor changes in DC resistance.
  • Perform Frequency Response Analysis (FRA) tests to establish a baseline for the mechanical state of the windings.
  • Monitor operating temperature to prevent overheating.

2. Short-Circuit Current Protection

  • Optimize relay protection settings to quickly clear short-circuit faults.
  • Install current-limiting devices to reduce the impact of short-circuit current.
  • Conduct winding deformation detection immediately after a short-circuit fault.

3. Mechanical State Inspection

  • Regularly inspect the condition of winding fasteners.
  • Judge the loosening of windings through acoustic detection.
  • Check if the supporting structure has displacement or deformation.

4. Environmental Control

  • Maintain a stable temperature in the transformer room to avoid drastic changes.
  • Control environmental humidity within a reasonable range.
  • Regularly clean the surface of the transformer to prevent dust accumulation from affecting heat dissipation.

V. Detection Technologies and Diagnostic Methods

1. Frequency Response Analysis (FRA)

  • Judge winding deformation by comparing frequency response curves from different periods.
  • Analyze impedance characteristics in the range of 10Hz-2MHz.
  • High sensitivity, capable of detecting minor deformations.

2. Short-Circuit Impedance Test

  • Measure changes in the transformer’s short-circuit impedance.
  • Pay attention if the impedance change exceeds 2%.
  • Simple and easy to implement, suitable for on-site applications.

3. Vibration Analysis Method

  • Monitor the vibration spectrum characteristics of the windings.
  • Judge the mechanical state through changes in vibration modes.
  • Enables online monitoring.

4. Ultrasonic Detection

  • Detect changes in the internal structure of the windings.
  • Good ability to identify local deformations.
  • Requires professional equipment and technical personnel.

VI. Preventive Maintenance Strategies

1. Establish a Condition Assessment System

  • Collect transformer design, manufacturing, and test data.
  • Record operational history and maintenance records.
  • Establish a complete equipment health file.

2. Formulate Regular Detection Plans

  • Determine the detection cycle based on the importance of the transformer and operating conditions.
  • Conduct a comprehensive assessment by combining multiple detection methods.
  • Pay special attention to transformers under heavy load or frequent start-stop operations.

3. Service Life Prediction and Risk Assessment

  • Evaluate the remaining mechanical life of the windings.
  • Predict the development trend of deformation.
  • Formulate targeted maintenance plans.

4. Spare Parts Management

  • Reserve key components to shorten the maintenance cycle.
  • Regularly replace vulnerable parts.
  • Ensure the quality and reliability of maintenance materials.

VII. Summary

Preventing winding deformation in dry-type transformers is a systematic project that requires comprehensive measures across design, manufacturing, operation, and maintenance phases. By optimizing the design to improve the inherent strength of the windings, strictly controlling the manufacturing process to ensure quality, implementing scientific operation and maintenance to maintain good conditions, and combining advanced detection technologies to timely identify hidden dangers, winding deformation can be effectively prevented, the service life of the transformer can be extended, and the safe and stable operation of the power system can be guaranteed.
The key to preventing winding deformation lies in the concept of "prevention first, combination of prevention and control" and establishing a full-life-cycle management philosophy to minimize the risk of deformation. With the advancement of detection technologies and the development of materials science, the prevention of winding deformation in dry-type transformers will become more accurate and effective.